Drainage pumps for Aspen Mini and Maxi Orange air conditioners. Drainage pumps for Aspen Mini and Maxi Orange air conditioners How to connect power to the maxi orange pump

Description

Mini Orange / AO Mini lift

Operating principle


Video

Mini Orange / AO Mini lift- the most popular model drain pump in the world. This pump has earned recognition from engineers and installers for its high reliability, ease of connection and a wide range of useful and high-quality accessories. In addition to standard fasteners, the standard delivery set includes an anti-siphon device and a submersible sensor housing. In addition, Aspen produces additional accessories from the XTRA extended set. The Mini Orange pump is ideal for both household air conditioners and small semi-industrial and industrial units with a power of up to 16 kW.

Operating principle

Switching Mini Orange on and off occurs based on a signal from an external level sensor, connected to the pump module using a control cable. The pump has an overflow protection circuit, when connected, you can control the air conditioner in emergency situations - for example, turn it off when the water reaches a critical level with sound and/or light signals.

The best-selling device for draining condensate liquid from household, semi-industrial, and industrial climate control equipment is a drainage pump for the Aspen Mini Orange air conditioner.

General characteristics

The Aspen Orange drainage pump is a separate type drainage system. It differs from other similar devices in its design features. Separate, they consist of several parts: a storage tank for collecting condensate and a pump, connected to each other using a drain pipe. Some models may have a separate control unit.

Thanks to the separate design, the systems have several hidden installation options, both in the indoor unit cooling equipment and outside it. This feature makes separate pumps one of the most popular for removing accumulated condensate from domestic and industrial air conditioning units.

Operating principle

The Aspen Orange drainage pump in its basic configuration is equipped with two reservoirs for collecting liquid (submersible and separately mounted). The use of these containers depends on the design features of the specific cooling equipment.

The tanks are installed in the pan itself and inside the air conditioner unit. The pump pump can be mounted inside the indoor unit itself or outside it in the ceiling space, wall niches, communication ducts, etc. Once connected, the diverter devices are capable of pumping excess liquid to a height of 10 m to 20 m (depending on the model).

Each tank has a float to determine the level of liquid in it. When the float reaches a certain height, the contacts close and a signal is received to turn on the drain system. The device will remove accumulated condensate until a new signal is received from the level sensor.

Equipped with overflow protection, which allows you to control them even in an unusual situation.

Scope of application – household, economic, industrial climate control devices.

The Maxi Orange drainage pump is distinguished by its high power, condensate rise height, and minimal operating noise level. This allows it to be installed in medical, public, domestic and industrial premises.

Can be mounted in larger units to provide additional power. Suitable for use in powerful climate control devices, removing large amounts of condensate over a horizontal distance of up to 100 m.

At the same time, the rather small size and weight allow the system to be discreetly installed in compact spaces and small rooms.

Drainage pump Aspen Mini Orange

The Mini Orange drainage pump stands out among its analogues with its compact size and good performance power. This main advantage allowed it to become the best-selling drainage system in the world. Possible installation in small-sized air conditioning systems in limited space. Has more low level noise compared to Maxi Orange, does not require additional participation in its work.

At the same time, it is distinguished by reliability, high quality, ease of installation and further service.

Installation of Aspen Orange systems

The installation is clearly presented in the video

Benefits of Aspen systems

They have a number of advantages compared to similar devices:

  • almost silent level of operation;
  • compact dimensions, allowing the system to be installed in the internal unit of climate control equipment or communication niches even in limited conditions, without disturbing the aesthetics of the apartment or office space;
  • optimal combination of compact size and production capacity of drainage systems;
  • high rates of removal of condensed liquid from climate systems;
  • condensate lifting height up to 2 m;
  • absolute sealing of drainage systems;
  • Aspen Orange thermal protection is provided;
  • the presence of an anti-siphon design;
  • availability of Plug-and-play concept;
  • easy access to the system during further service and care;
  • reasonable price.

In many respects, these devices are recognized as one of the best in the segment of devices for draining condensate in climate-controlled, refrigeration equipment. Thanks to your design features, small sizes, high productivity power, ease of connection and maintenance, high-quality equipment, a variety of related accessories and reasonable price Aspen Orange are in great demand among consumers. Its reliability, operating efficiency, high quality These systems have proven comfortable use over many years.

Friends! More interesting materials:

Oh! There are no materials yet(((. Browse the site again!

Pump ASPEN MINI ORANGE

INCLUDED price 4800.00 rub.

1. Mini Orange pump

2. The reservoir consists of:

A. Cover and touch cable

B. float with magnet

C. filter mesh

d. tank body

3. Submersible tank

4. Vinyl tube: length 15 cm,

Diameter 6 mm

5. Entrance drainage tube

6. Vinyl tube: length 1.5m,

Diameter 6 mm

7. 1 6 pin socket

8. Clamps 300mm x 3.6mm (4 pcs)

9. Clamps 140mm x 3.6mm (2 pcs)

10. Self-adhesive pile

Velcro tape (2 pcs)

* NOTE: You will need several

meters of vinyl tube outer diameter

rum 9 mm and inner diameter 6 mm

TECHNICAL SPECIFICATIONS

Power supply 220-240 V - 16 W Water flow rate 14 l/h per
1 phase 50/60 Hz zero altitude
3 A signal wires are not under Maximum water temperature 40 C
voltage, N.O. (Fine Maximum recommended height
open) N.C. (Fine lift 8 m
closed) Noise level: 23 dB(A) - distance 1 m
Long operating time Outlet tube: internal diameter 6 mm
Hall effect water with high CE mark
degree of safety Thermal protection
Completely sealed

PERFORMANCE CHART

SAFETY

WARNING: Pump Mini Orange Do not turn on the pump without water.
It only pumps out water. make sure that the magnet is in
Attention! There is a risk of electrical damage the float is at the top.
tric current. This pump is not intended Be sure to make sure that the tank
for use in swimming pools and is in a horizontal position.
coastal areas. The pump fits perfectly
Insulating electrical contacts for all industrial, residential
must match all and office space. However, not
the requirements placed on it. It is recommended to use the pump in
Make sure the pump is de-energized before especially in dusty conditions and
installation and service. working with oily substances.
If electrical wire damaged, Suitable for use only
then it must be replaced with the same one indoors.
or similar. Doesn't work underwater.

PREVENTION OF AIR CLOCK FORMATION

Position the drain pipe above the water level in the indoor unit and insert its end into the wider drain pipe.

1. Suspended ceiling 2. End of drain pipe 3. Water level in pan 4. Air brake 5. Top of anti-formation pipe air jams

INSTALLATION

1 You choose the type of tank


2 Make sure the float in the reservoir is positioned with the magnet facing up, the filter is installed, and the reservoir lid is tightly closed.

4 Place the anti-air tube onto the fitting on the tank lid.

5 Install the pump block behind suspended ceiling, where possible.

1. False ceiling 2. Evaporator coil 3. Condensate tray 4. Vinyl pipe 5. Plastic box

6

7 Pay attention to the direction of water movement

8 Place a tube with an outer diameter of 9 mm and an inner diameter of 6 mm onto the reservoir and pump. Secure the connections using clamps. Make sure that the length of the tube does not exceed 2 m.

9

10 In order to emergency turn off the air conditioner in case of improper functioning of the pump, in The air conditioner must have a built-in emergency switch.
Please note: This instruction is an example of how the pump can be installed and is provided for reference only. All pumps must be installed by qualified personnel.


11 To check the pump operation, pour water into the evaporator tray. Make sure connections are tight